Class 1 Unit of IDEX Corporation
607 NW 27th Avenue Ocala, FL 34475 U.S.A.
Phone: 1-800-533-3560 352-629-5020
Fax: 1-800-5230-3473 352-629-2902
Web........www.class1.com
Manual p/n: 120339 Rev 10/13/09
13. When the calibrated measuring
container is lled to the required level,
press the red ON/OFF button ( )to
STOP foam ow. (See Figure 5.)
14. Use the INCREASE or DECREASE
buttons ( or ) and set the value to
the known amount of foam collected in
the calibrated measuring container.
15. If the foam is dispensed into a clean
container, return the concentrate to the
foam tank and place the bypass hose
back into the container.
IMPORTANT !
If the container is NOT clean, the foam becomes
contaminated and must be discarded.
16. Repeat preceding Steps 12 through 14.
17. Press the DISPLAY button (
i) to view
the foam ow calibration factor. Write
this number down for future reference.
(See Figure 6).
Verify that the foam calibration factor is
between 270 and 310.
Contact customer service at 1-800-533-3569
if the calibration factor does not fall within the
required calibration range.
18. Press and hold the DISPLAY button (
i)
until PASS is displayed. (See Figure 1
on the preceding page.)
19. With the DISPLAY button (
i) pressed,
press the INCREASE button ( ) 4 times.
A u is shown with each INCREASE
button press. (See Figure 2 on the
preceding page.)
20. Release the DISPLAY button (
i). The
display shows ScAL for about 5 seconds.
The unit re-initializes and the calibration
factor is saved. (See Figure 7.)
21. Foam ow calibration is now complete.